ESTONIA
|
Gas Family |
|
|||
|
Gas Group |
|
|||
|
|
min |
max |
||
|
Gross Calorific Value (GCV) [MJ/m3] |
35,53 |
- |
||
|
Wobbe index [MJ/m3] |
47,89 |
52,95 |
||
|
Gas composition by volume in % of the total content: |
||||
|
C1 to C5 content (sum) |
- |
100 |
||
|
N2 + CO2 content |
N2 < 3 / CO2 < 2,5 |
|||
|
CO content |
- |
- |
||
|
Unsaturated HC content |
- |
- |
||
|
Hydrogen content |
- |
0,1 |
||
|
Information on toxic components contained in the gaseous fuel |
|
|||
|
Supply pressure: |
||||
|
|
min |
nom |
max |
|
|
Supply pressure at the inlet of appliances [mbar] |
18 |
20 |
25 |
|
|
Supply pressure at the point of delivery [mbar] |
18 |
23 |
25 |
|
|
admissible pressure loss in the end-user gas installation [mbar] |
1,0 |
1,5 |
2,0 |
|
|
Reference conditions for Wobbe index and Gross Calorific Value (GCV) |
||||
|
Combustion reference temperature [°C] |
15 °C |
|||
|
Volume measurement reference temperature [°C] |
15 °C |
|||
|
Volume measurement reference pressure [mbar] |
1 013,25 mbar |
|||
GREECE
1. Types of gas:
The following types of gas are distributed in Greece:
|
— |
gases in group H (2H) of the 2nd family (natural gas), and |
|
— |
gases in all three groups of the 3rd family (liquefied petroleum gas):
|
2. Legislation:
Natural gas:
|
1. |
Ministerial Decision No Δ3/Α΄/οικ.6598/20.03.2012 on the technical regulation on internal natural gas installations operating at pressures of up to 500mbar (Government Gazette, Series II, No 976) |
|
2. |
Amendment No Ε-143/2023 of the Management Code for the National Natural Gas System (ESFA) (9th revision) (GG II 5773) |
|
3. |
Regulation (EU) 2015/703 establishing a network code on interoperability and data exchange rules (Annex - Conversion factors between reference conditions) |
Liquefied petroleum gas:
|
1. |
Joint Ministerial Decision No 31856/11.08.2003 on the technical regulation on LPG installations in buildings (other than factories and small-scale industries) (GG II 1257) |
|
2. |
Joint Ministerial Decision No 300/2005/18.09.2006 on LPG specifications (GG II 1483). |
3. Types of gas and corresponding gas supply pressures in accordance with Article 4 of Regulation (EU) 2016/426
|
Gas Family |
2nd Family |
3rd Family |
||||||||||||||
|
Gas Group |
Group H |
Group P |
Group P/B |
Group B |
||||||||||||
|
|
min |
max |
min |
max |
min |
max |
min |
max |
||||||||
|
Gross Calorific Value (GCV) [MJ/m3] |
34,75 |
46,70 |
87,48 |
95,40 |
108,72 |
118,80 |
115,92 |
126,36 |
||||||||
|
Wobbe index [MJ/m3] |
44,63 |
55,77 |
72,90 |
76,80 |
72,90 |
87,30 |
81,80 |
87,30 |
||||||||
|
Gas composition by volume in % of the total content: |
||||||||||||||||
|
C1 to C5 content in % (sum) [% mole] |
||||||||||||||||
|
C1 content in % (sum) [% mole] |
75 |
|||||||||||||||
|
C4 content in % (sum) [% mole] |
5 |
|||||||||||||||
|
C5 content in % (sum) [% mole] |
2 |
2 |
2 |
|||||||||||||
|
N2 content [% mole] |
6,0 |
|||||||||||||||
|
CO2 content [% mole] |
3,0 |
|||||||||||||||
|
CO content [% mole] |
||||||||||||||||
|
unsaturated HC content [% mole] |
||||||||||||||||
|
Hydrogen content [% mole] |
||||||||||||||||
|
Information on toxic components contained in the gaseous fuel |
||||||||||||||||
|
H2S [mg/Nm3] |
5,4 (2) |
|
0 |
|
0 |
|
0 |
|||||||||
|
CO content [% mole] |
||||||||||||||||
|
1,3-butadiene [% mole] |
- |
- |
0,5 |
0,5 |
0,5 |
|||||||||||
|
Supply pressure: |
||||||||||||||||
|
|
min |
nom |
max |
min |
nom |
max |
min |
nom |
max |
min |
nom |
max |
||||
|
Supply pressure at the point of delivery [mbar] |
17 |
20 |
25 |
25 |
37 |
45 (3) |
25 |
29 |
35 (3) |
20 |
29 |
35 (3) |
||||
|
admissible pressure loss in the end-user gas installation [mbar] |
2,0 |
2,0 |
2,0 |
2,0 |
2,0 |
2,0 |
||||||||||
|
Reference conditions for Wobbe index and Gross Calorific Value (GCV) |
||||||||||||||||
|
Combustion reference temperature [°C] |
15 °C |
|||||||||||||||
|
Volume measurement reference temperature [°C] |
15 °C |
|||||||||||||||
|
Volume measurement reference pressure [mbar] |
1 013,25 mbar |
|||||||||||||||
HUNGARY
|
Gas Family |
2nd Family |
3rd Family |
||||||||||||||
|
Gas Group |
Group H |
Group S |
Group B/P |
Group P |
||||||||||||
|
|
min |
max |
min |
max |
min |
max |
min |
max |
||||||||
|
Gross Calorific Value (GCV) [MJ/m3] |
31,46 |
41,01 |
27,94 |
32,6 |
88,52 |
125,81 |
88,52 |
95,65 |
||||||||
|
Wobbe index [MJ/m3] |
45,66 |
54,69 |
36,29 |
41,58 |
72,86 |
87,33 |
72,86 |
76,84 |
||||||||
|
Gas composition by volume in % of the total content: |
||||||||||||||||
|
C1 to C5 content (sum) |
91 |
100 |
82 |
86 |
99,6 |
100 [m/m%] C4: max 60 [m/m%] C5: max 2 [m/m%] |
99,6 [m/m%] C3: min 95 [m/m%] |
100 [m/m%] C5: max 0,2 [m/m%] |
||||||||
|
N2 + CO2 content |
0 |
2,5 |
14 |
18 |
N2 + O2 + H2: max 0,2 [m/m%] |
|||||||||||
|
CO content |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
||||||||
|
Unsaturated HC content |
0 |
0 |
0 |
0 |
mono-olefins: max 10 [m/m%] dienes: max 0,5 [m/m%] |
|||||||||||
|
Hydrogen content |
0 |
0 |
- |
- |
N2 + O2 + H2: max 0,2 [m/m%] |
|||||||||||
|
Information on toxic components contained in the gaseous fuel |
technically free |
technically free |
technically free |
technically free |
||||||||||||
|
Supply pressure: |
||||||||||||||||
|
|
min |
nom |
max |
min |
nom |
max |
min |
nom |
max |
min |
nom |
max |
||||
|
Supply pressure at the inlet of appliances [mbar] (4) |
18 (73 ) |
25 (85 ) |
33 (100 ) |
18 (73 ) |
25 (85 ) |
33 (100 ) |
25 (42,5 ) |
29 (50 ) |
35 (57,5 ) |
25 (42,5 ) |
29 (50 ) |
35 (57,5 ) |
||||
|
Supply pressure at the point of delivery [mbar] |
Value identified by the gas licensee for the connection point of the manifold system and the connecting line |
|||||||||||||||
|
admissible pressure loss in the end-user gas installation [mbar] |
Depends on the make of the gas installation |
|||||||||||||||
|
Reference conditions for Wobbe index and Gross Calorific Value (GCV) |
||||||||||||||||
|
Combustion reference temperature [°C] |
15 °C |
|||||||||||||||
|
Volume measurement reference temperature [°C] |
15 °C |
|||||||||||||||
|
Volume measurement reference pressure [mbar] |
1 013,25 mbar |
|||||||||||||||
MALTA
|
Gas Family |
3rd Family |
|||
|
Gas Group |
|
|||
|
|
min |
max |
||
|
Gross Calorific Value (GCV) [MJ/m3] |
||||
|
Wobbe index (6) [MJ/m3] |
72,9 |
87,3 |
||
|
Gas composition by volume in % of the total content: |
||||
|
C1 |
||||
|
C2 |
||||
|
C3 |
||||
|
C4 |
||||
|
C5 |
||||
|
C6 |
||||
|
N2 + CO2 content in % |
||||
|
CO content in % |
||||
|
Unsaturated HC content in % |
||||
|
Hydrogen content in % |
||||
|
Supply pressure: |
||||
|
|
min |
nom |
max |
|
|
Supply pressure at the inlet of appliances [mbar] |
28 |
- |
30 |
|
|
Supply pressure at the point of delivery [mbar] |
||||
|
admissible pressure loss in the end-user gas installation [mbar] |
||||
SLOVAKIA
|
Gas Family |
|
|||
|
Gas Group |
|
|||
|
|
min |
max |
||
|
Gross Calorific Value (GCV) [MJ/m3] |
38,5 |
38,9 |
||
|
Wobbe index [MJ/m3] |
49,0 |
50,8 |
||
|
Gas composition by volume in % of the total content: |
||||
|
C1 to C5 content (sum) |
98,2 |
99,2 |
||
|
N2 + CO2 content |
0,8 |
1,8 |
||
|
CO content |
n/a (9) |
n/a (9) |
||
|
Unsaturated HC content |
n/a (9) |
n/a (9) |
||
|
Hydrogen content |
n/a (9) |
n/a (9) |
||
|
Information on toxic components contained in the gaseous fuel |
Information on toxic components is not available to the distribution system operator. Natural gas distributed in the territory of the Slovak Republic is odourised and does not have toxic or poisoning effects. A component – odorant – used for this purpose is toxic only to aquatic organisms. |
|||
|
Supply pressure: |
||||
|
|
min |
nom |
max |
|
|
Supply pressure at the inlet of appliances (10) [mbar] |
17 |
20 |
25 |
|
|
Supply pressure at the point of delivery [mbar] |
n/a |
n/a |
n/a |
|
|
admissible pressure loss in the end-user gas installation [mbar] |
n/a |
n/a |
n/a |
|
|
Reference conditions for Wobbe index and Gross Calorific Value (GCV) |
||||
|
Combustion reference temperature [°C] |
15 °C |
|||
|
Volume measurement reference temperature [°C] |
15 °C |
|||
|
Volume measurement reference pressure [mbar] |
1 013,25 mbar |
|||
(1) Not regulated.
(2) In special circumstances and not more than 2 hours it may contain double quantity but the daily average value must be less than 6,5 mg/Nm3.
(3) It concerns installations of liquefied petroleum gas except industrial and craft industries.
(4) Comments:
For ‘Supply pressure at the inlet of appliances’, data in parentheses refer to elevated low pressure gas networks.
(5) Not specified
(6) Based on the definition of LPG found in the Liquefied Petroleum Gas Market Regulations (Legal Notice 249 of 2008) as amended
(7) Not regulated
(8) Not applicable
(9) These data are not analysed by the distribution network operator and are therefore not available.
(10) This is the input pressure for appliances that are connected to the distribution network; appliances connected to pressure vessels are also used in the Slovak Republic.
ELI: http://data.europa.eu/eli/C/2025/2463/oj