This text is meant purely as a documentation tool and has no legal effect. The Union's institutions do not assume any liability for its contents. The authentic versions of the relevant acts, including their preambles, are those published in the Official Journal of the European Union and available in EUR-Lex. Those official texts are directly accessible through the links embedded in this document
|
COMMISSION DECISION of 17 January 2003 establishing the classes of reaction-to-fire performance for certain construction products (notified under document number C(2002) 4807) (Text with EEA relevance) (OJ L 013 18.1.2003, p. 35) |
Amended by:
|
|
|
Official Journal |
||
|
No |
page |
date |
||
|
L 201 |
25 |
8.8.2003 |
||
|
L 276 |
77 |
7.10.2006 |
||
|
L 131 |
21 |
23.5.2007 |
||
Corrected by:
COMMISSION DECISION
of 17 January 2003
establishing the classes of reaction-to-fire performance for certain construction products
(notified under document number C(2002) 4807)
(Text with EEA relevance)
(2003/43/EC)
Article 1
The construction products and/or materials which satisfy all the requirements of the performance characteristic ‘reaction-to-fire’ without need for further testing are set out in the Annex.
Article 2
The specific classes to be applied to different construction products and/or materials, within the reaction-to-fire classification adopted in Decision 2000/147/EC, are set out in the Annex to this Decision.
Article 3
Products shall be considered in relation to their end-use application, where relevant.
Article 4
This Decision is addressed to the Member States.
ANNEX
The tables set out in this annex list construction products and/or materials which satisfy all the requirements for the performance characteristic reaction to fire without need for testing.
Table 1
Classes of reaction to fire performance for wood-based panels
|
Product |
EN product standard |
End use condition (6) |
Minimum density (kg/m3) |
Minimum thickness (mm) |
Class (7) (excluding floorings) |
Class (8) (floorings) |
|
Cement-bonded particleboard (1) |
EN 634-2 |
without an air gap behind the panel |
1 000 |
10 |
B-s1, d0 |
Bfl-s1 |
|
Fibreboard, hard (1) |
EN 622-2 |
without an air gap behind the wood-based panel |
900 |
6 |
D-s2, d0 |
Dfl-s1 |
|
Fibreboard, hard (3) |
EN 622-2 |
with a closed air gap not more than 22 mm behind the wood-based panel |
900 |
6 |
D-s2, d2 |
— |
|
EN 312 |
without an air gap behind the wood-based panel |
600 |
9 |
D-s2, d0 |
Dfl-s1 |
|
|
EN 622-2 EN 622-3 |
||||||
|
EN 622-5 |
||||||
|
EN 300 |
||||||
|
EN 636 |
-“- |
400 |
9 |
D-s2, d0 |
Dfl-s1 |
|
|
EN 13353 |
12 |
|||||
|
EN 15197 |
-“- |
450 |
15 |
D-s2, d0 |
Dfl-s1 |
|
|
EN 312 |
with a closed or an open air gap not more than 22 mm behind the wood-based panel |
600 |
9 |
D-s2, d2 |
— |
|
|
EN 622-2 EN 622-3 |
||||||
|
EN 622-5 |
||||||
|
EN 300 |
||||||
|
EN 636 |
-“- |
400 |
9 |
D-s2, d2 |
— |
|
|
EN 13353 |
12 |
|||||
|
EN 312 |
with a closed air gap behind the wood-based panel |
600 |
15 |
D-s2, d0 |
Dfl-s1 |
|
|
EN 622-3 |
||||||
|
EN 622-5 |
||||||
|
EN 300 |
||||||
|
EN 636 |
-“- |
400 |
15 |
D-s2, d1 |
Dfl-s1 |
|
|
EN 13353 |
D-s2, d0 |
|||||
|
EN 15197 |
-“- |
450 |
15 |
D-s2, d0 |
Dfl-s1 |
|
|
EN 312 |
with an open air gap behind the wood-based panel |
600 |
18 |
D-s2, d0 |
Dfl-s1 |
|
|
EN 622-3 |
||||||
|
EN 622-5 |
||||||
|
EN 300 |
||||||
|
EN 636 |
-“- |
400 |
18 |
D-s2, d0 |
Dfl-s1 |
|
|
EN 13353 |
||||||
|
EN 15197 |
-“- |
450 |
18 |
D-s2, d0 |
Dfl-s1 |
|
|
Particleboard (5) |
EN 312 |
any |
600 |
3 |
E |
Efl |
|
OSB (5) |
EN 300 |
|||||
|
MDF (5) |
EN 622-5 |
-“- |
400 |
3 |
E |
Efl |
|
250 |
9 |
E |
Efl |
|||
|
Plywood (5) |
EN 636 |
-“- |
400 |
3 |
E |
Efl |
|
Fibreboard, hard (5) |
EN 622-2 |
-“- |
900 |
3 |
E |
Efl |
|
Fibreboard, medium (5) |
EN 622-3 |
-“- |
400 |
9 |
E |
Efl |
|
Fibreboard, soft |
EN 622-4 |
-“- |
250 |
9 |
E |
Efl |
|
(1)
Mounted without an air gap directly against class A1 or A2-s1, d0 products with minimum density 10 kg/m3 or at least class D-s2, d2 products with minimum density 400 kg/m3.
(2)
A substrate of cellulose insulation material of at least class E may be included if mounted directly against the wood-based panel, but not for floorings.
(3)
Mounted with an air gap behind. The reverse face of the cavity shall be at least class A2-s1, d0 products with minimum density 10 kg/m3.
(4)
Mounted with an air gap behind. The reverse face of the cavity shall be at least class D-s2, d2 products with minimum density 400 kg/m3.
(5)
Veneered, phenol- and melamine-faced panels are included for class excl. floorings.
(6)
A vapour barrier with a thickness up to 0,4 mm and a mass up to 200 g/m2 can be mounted in between the wood-based panel and a substrate if there are no air gaps in between.
(7)
Class as provided for in Table 1 of the Annex to Decision 2000/147/EC.
(8)
Class as provided for in Table 2 of the Annex to Decision 2000/147/EC. |
||||||
Table 2
Classes of reaction — to — fire performance of gypsum plasterboards
|
Gypsum plasterboard |
Nominal board thickness (mm) |
Gypsum core |
Paper grammage (1) (g/m2) |
Substrate |
Class (2) (excluding floorings) |
|
|
Density (kg/m3) |
Reaction to fire class |
|||||
|
Conforming to EN 520 (except perforated boards) |
≥ 6,5 < 9,5 |
≥ 800 |
A1 |
≤ 220 |
Any wood-based product with density ≥ 400 kg/m3 or any product of at least class A2-s1, d0 |
A2-s1, d0 |
|
> 220 ≤ 320 |
B-s1, d0 |
|||||
|
≥ 9,5 |
≥ 600 |
≤ 220 |
Any wood-based product with density ≥ 400 kg/m3 or any product of at least class A2-s1, d0 or any insulating product of at least class E-d2 mounted according to method 1 |
A2-s1, d0 |
||
|
> 220 ≤ 320 |
B-s1, d0 |
|||||
|
(1)
Determined according to EN ISO 536 and with no more than 5 % organic additive content.
(2)
Classes as provided for in Table 1 of the Annex to Commission Decision 2000/147/EC. |
||||||
The gypsum plasterboards (hereinafter — ‘gypsum boards’) shall be mounted and fixed using one of the three following methods:
any wood-based product with density ≥ 400 kg/m3 or any product of at least class A2-s1, d0 in case of gypsum boards of ≥ 6,5 mm and < 9,5 mm nominal thickness and ≥ 800 kg/m3 core density, or
any wood-based product with density ≥ 400 kg/m3 or any product of at least class A2-s1, d0 in case of gypsum boards of ≥ 9,5 mm nominal thickness and ≥ 600 kg/m3 core density, or
any insulating material of at least class E-d2 in case of gypsum boards of ≥ 9,5 mm nominal thickness and ≥ 600 kg/m3 core density.
Table 3
Classes of reaction-to-fire performance of high-pressure decorative laminate panels
|
High pressure decorative laminate panels (1) |
Product detail |
Minimum density (kg/m3) |
Minimum overall thickness (mm) |
Class (2) (excluding floorings) |
|
Interior grade non-FR Compact HPL panels (3) |
Compact HPL meeting EN 438-4 type CGS |
1 350 |
6 |
D-s2, d0 |
|
Interior grade non-FR HPL composite panels with wood-based substrates (3) |
Composite panels comprising non-FR grade HPL meeting the requirements of EN 438-3, adhesively bonded to both sides of non-FR grade wood-based core of minimum thickness 12 mm complying with EN 13986, using PVAc or thermosetting adhesive at an application rate of 60 to 120 g/m2 |
Wood-based core minimum density 600 HPL minimum density 1 350 |
12 mm wood-based core with HPL ≥ 0,5 mm bonded to both sides |
D-s2, d0 |
|
(1)
Either directly fixed (i.e. with no air gap) to a material having a reaction to fire of A2-s1, d0 or better and a density of at least 600 kg/m3, or mounted on a timber or metal batten support frame, with a non-ventilated (i.e. void open only at the top) air gap of at least 30 mm, the reverse face of the cavity so formed having a reaction to fire classification of A2-s1, d0 or better.
(2)
Classes as provided for in Table 1 of the Annex to Decision 2000/147/EC.
(3)
Complying with European Standard EN 438-7. |
||||
Table 4
Classes of reaction-to-fire performance of structural timber products (1)
|
|
Product detail |
Minimum mean density (3) (kg/m3) |
Minimum overall thickness (mm) |
Class (2) (excluding floorings) |
|
Structural timber |
Visual and machine graded structural timber with rectangular cross-sections shaped by sawing, planing or other methods or with round cross-sections |
350 |
22 |
D-s2, d0 |
|
(1)
Applies to all species covered by the product standards.
(2)
Classes as provided for in Table 1 of the Annex to Decision 2000/147/EC.
(3)
Conditioned according to EN 13238. |
||||
( 1 ) OJ L 40, 11.2.1989, p. 12.
( 2 ) OJ L 220, 30.8.1993, p. 1.
( 3 ) OJ C 62, 28.2.1994, p. 1.’
( 4 ) OJ L 50, 23.2.2000, p. 14.